Care home fire risk assessments: key facts
- In England and Wales the Fire Safety Order requires a suitable and sufficient fire risk assessment, recorded in full. The care provider, as employer, is normally the responsible person.
- The Home Office has a specific guide for care homes: Fire safety risk assessment: residential care premises, published under Article 50 of the Fire Safety Order.
- In care homes, progressive horizontal evacuation is normally adopted: residents near the fire are moved to an adjoining protected area on the same floor.
- The Home Office guide says the number of beds in each protected area should depend on the minimum number of staff awake, normally the night-time staffing level.
- You should not depend on the fire and rescue service to evacuate residents. The evacuation plan must work with your own staff.
- Premises where people sleep must have automatic fire detection.
- CQC asks care homes applying to register for a copy of their current fire risk assessment, covering PEEPs, medical gas storage and smoking policies. Fire safety law itself is enforced by fire and rescue authorities.
- In Scotland, government guidance says care home fire drills should take place at least twice a year, with every member of staff taking part at least once a year.
What makes a care home fire risk assessment different?
Residents sleep there, and many cannot escape without staff. So the assessment is less about how fast people can walk out and more about whether the building holds back fire long enough, and whether the staff on shift can move everyone in time.
In an office or shop, a fire risk assessment mostly checks that people can get out quickly by themselves. In a care home that assumption fails. Many residents are frail, some are in bed, some take medication that makes them hard to wake, and some will not understand what the alarm means. The Home Office guide asks you to judge each resident's mobility, their awareness and how much co-operation staff can expect from them.
That changes what the assessment has to answer:
- Can the building buy time? Fire-resisting walls, fire doors and protected areas must hold back fire and smoke while staff work.
- Will the fire be found early? Where people sleep, the alarm must include automatic detection.
- Can the staff on duty carry out the plan? At night there are fewer staff and most residents are asleep. The Home Office guide treats this as the usual worst case.
- Does each resident have a plan? Personal emergency evacuation plans (PEEPs) record how each person will be moved.
- Is the plan practised? Drills need to include night staff and night-time conditions.
The Home Office makes the same point about assessors. Its 2023 guide says someone with plenty of experience of offices, factories and shops "might not have adequate experience" to assess a residential care home. Experience of care premises is the first thing to check when you choose one.
The risk is real. The Scottish Government's care home guidance recalls the Rosepark Care Home fire in 2004. A short, fast-developing fire started in a cupboard in a bedroom corridor, and 14 residents died from smoke and toxic gases.
Which law applies, and who is the responsible person in a care home?
In England and Wales it is the Regulatory Reform (Fire Safety) Order 2005. The responsible person is normally the care provider as employer, plus anyone else who controls part of the building, such as a landlord.
Under the Fire Safety Order, the responsible person in a workplace is the employer, if the workplace is to any extent under their control. In most care homes that is the registered provider: the company, charity, partnership or individual that runs the service and employs the staff. The registered manager usually runs fire safety day to day, but the duty sits with the organisation.
Others can share duties:
- A landlord or building owner who keeps control of the structure or shared systems has duties for the things they control. CQC reminds tenant providers that the Fire Safety Order still places fire safety duties on them for their employees, even if a landlord manages the building.
- Contractors who maintain the alarm, emergency lighting or fire doors under contract are treated as having control to that extent.
- Directors and managers can be personally liable for an offence committed with their consent or connivance, or caused by their neglect.
The responsible person must:
- Make a suitable and sufficient fire risk assessment, and record it in full, including any group of people especially at risk. In a care home, that is most residents.
- Record the name of anyone they engaged to carry out or review it (England and Wales, since 1 October 2023).
- Appoint one or more competent people to help with the preventive and protective measures (article 18).
- Review the assessment regularly, and whenever something significant changes.
- Find out whether anyone else has fire safety duties for the building and share contact details with them.
Local fire and rescue authorities enforce the Fire Safety Order. They can inspect, give advice, and serve alterations, enforcement or prohibition notices. Serious failures can lead to prosecution, with unlimited fines and up to two years in prison.
What does CQC expect, and is CQC the fire safety enforcer?
No. CQC regulates the safety and quality of care; fire safety in buildings is mainly regulated by fire and rescue services. But CQC asks care homes applying to register for a copy of their current fire risk assessment, and it checks premises safety under regulations 12 and 15.
Care home managers often hear about fire safety from two directions. It helps to know who does what.
| Fire and rescue authority | CQC (England) | |
|---|---|---|
| Law it uses | Regulatory Reform (Fire Safety) Order 2005 | Health and Social Care Act 2008 (Regulated Activities) Regulations 2014 |
| Main focus | Fire safety in the building | Safety and quality of care, including safe premises |
| What it can do | Inspect, serve fire safety notices, prosecute | Refuse registration, take regulatory action |
CQC's memorandum of understanding with the National Fire Chiefs Council (signed July 2020) says the primary regulatory responsibility for fire safety in buildings sits with fire and rescue services and local authorities, and responsibility for the safety of care sits with CQC. Fire services may share information with CQC about fires at locations it regulates, and both agree to engage early where they see risks.
CQC still cares about fire safety:
- Regulation 12 (safe care and treatment) requires providers to ensure the premises are safe to use for their intended purpose and are used in a safe way. CQC's guidance says providers need systems that assure compliance with statutory requirements, and plans for emergencies such as fires.
- Regulation 15 (premises and equipment) requires premises to be suitable, properly used and properly maintained. CQC lists the Fire Safety Order among the legislation related to this regulation.
- Contracting out doesn't move responsibility. CQC says providers keep legal responsibility when they delegate to contractors.
What CQC says a care home's fire risk assessment should cover (registration guidance):
- Fire hazards, including medical gas storage
- People at risk
- Plans for people who need support to evacuate, including PEEPs
- Policies for smoking on the premises
- Evaluation of risks and existing fire safety measures
- Fire alarm systems, extinguishers and other firefighting equipment
- Fire exits and evacuation routes
- Staff training
- Fire drills for staff, people who use the service and visitors
- An action plan for concerns identified
CQC also says you must complete any actions your fire risk assessment identifies before you apply to register.
What is progressive horizontal evacuation, and when is it used?
Staff move residents near the fire through a fire-resisting barrier into the next protected area on the same floor. Residents wait there in relative safety, and move further only if needed. The Home Office says it is normally adopted in care homes.
The Home Office residential care guide describes three strategies. A care home may use more than one.
| Strategy | How it works | When the guide says it fits |
|---|---|---|
| Single stage evacuation | Everyone leaves the building at once | Mainly residents who can leave without help, or with minimal help |
| Progressive horizontal evacuation | Residents move through a fire-resisting barrier to an adjoining protected area on the same level, then further if needed | Where residents depend on staff to help them escape |
| Delayed evacuation | Some residents stay in their room while the fire is dealt with | Exceptionally, for example where a resident is attached to medical equipment such as oxygen therapy and can't be moved quickly |
Delayed evacuation is not a shortcut. The guide says a bedroom used this way needs enhanced structural fire protection, and you still need an evacuation plan for it.
The guide groups residents by how much they rely on staff:
- Independent: can leave without staff help, or with minimal help from one person.
- Dependent: everyone else, apart from very high dependency residents. This includes people with mental health problems, whatever their mobility.
- Very high dependency: people whose care or condition means immediate evacuation could be life threatening.
Two rules run through the guide. First, you should not depend on the fire and rescue service to evacuate people. Your strategy must rely only on things within your control. Second, consult your enforcing authority when you plan the strategy.
Timing matters too. The 2023 Home Office guide notes that some premises allow a short investigation before evacuating when a detector goes off by day, and that this "might not be acceptable during the night". Your assessor should check what your fire procedure says about this.
Can your night staff carry out the evacuation plan?
They must be able to. The Home Office guide says beds per protected area should depend on the minimum number of staff awake, normally the night shift, and that staff numbers must always be enough to carry out the emergency plan.
This is the question that most separates a care home assessment from other premises. Rotas are usually set for care needs. The fire risk assessment asks a different question: if a fire starts at 3am, can the people on shift move everyone in the affected area to safety in time?
The Home Office residential care guide says:
- The number of resident beds in each sub-compartment should depend on the minimum number of staff who are awake and available, normally the night-time staffing level.
- Your risk assessment should identify how many staff you need to carry out your emergency plan, and staff numbers at all times must be sufficient.
- Evacuation time depends on residents' mobility and awareness, the distance to the next protected area, the number of staff and their training.
- The worst case to plan for is usually when the fewest staff are on duty, for example at night when residents are asleep.
Scotland's 2022 guidance is just as direct. A small number of staff cannot be expected to move large numbers of high dependency residents, and difficulties are likely to be worse at night. It says the number of high dependency residents in a sub-compartment should be capable of being evacuated by the staff on duty at night before fire makes evacuation impractical.
Practical points an assessor may raise:
- Where residents sleep. Mixing lower and higher dependency residents in each area, or moving residents who need most help nearer a protected area, can make the plan workable. Dependency changes, so this needs revisiting.
- Agency and new staff. The guide lists agency or temporary staff and care staff working alone, especially at night, among people especially at risk.
- Evidence. Timed night-time drills or simulations show whether your staffing works. Assumptions alone do not.
- Changes. A cut in night staff, new residents with higher needs, or more beds in one wing are all reasons to review the assessment.
What alarms, compartmentation and fire doors does a care home need?
Almost every care home needs an electrical fire alarm with automatic detectors, sounders and call points. Fire-resisting construction must divide the building into protected areas, and fire doors must close automatically when the alarm sounds.
Detection and warning. The 2023 Home Office guide says premises where people sleep must have automatic fire detection. The residential care guide adds that virtually all premises it covers need an electrical system with automatic detectors, sounders and manual call points. Only very small homes (ground and first floor, up to four residents) may manage with interconnected smoke alarms. In Scotland, government guidance says the normal standard for a care home is a category L1 system under BS 5839-1, meaning automatic detection throughout, including roof spaces and voids.
Compartmentation. Progressive horizontal evacuation only works if each protected area really resists fire and smoke. Assessors look for gaps around pipes and cables, holes left by contractors, damaged ceilings and missing fire stopping in roof voids. The Home Office guide says fires are more frequent during building work, so review the assessment before refurbishment starts.
Fire doors and hold-open devices. Self-closing doors can trap or obstruct residents in daily life, which leads to doors being wedged open. The Home Office guide's answer:
- Fit controlled door closers with an electromagnetic hold-open (or free-swing) function that lets the door close when the fire alarm actuates. Wedges defeat the door completely.
- Where such devices are fitted, close the doors at night, and set a routine for closing corridor compartment doors at night.
- Bedroom doors may also have hold-open or free-swing devices that operate immediately the alarm actuates.
- Check regularly that the doors release and close. The Home Office says functions the fire alarm triggers, such as releasing doors or locks, need regular checks.
The guide puts it simply: "A care home is not a prison." Fire precautions should not make residents' lives worse than they need to. Good hold-open devices let residents move freely without wedges.
Fire doors take heavy daily wear in care homes from wheelchairs, hoists and trolleys. A damaged door, a broken closer or a missing seal can let smoke into the next protected area, so check them often and fix faults quickly.
Which fire hazards will an assessor look for in a care home?
Smoking residents, oxygen and other medical gases, laundry, kitchens, electrical equipment, stored linen and aerosols, and bedding used for pressure care. Each has specific guidance in the Home Office care guide.
- Smoking. The guide says your risk assessment must take account of residents who wish to smoke in their own rooms, and smokers confined to bed who can't reach a smoking area. It suggests a safe smoking policy with designated areas, a ban in laundries, storerooms and protected routes, and checks of smoking areas once they are empty at night.
- Oxygen and medical gases. Control the use and storage of oxygen cylinders and piped oxygen: no leaks, never used to "sweeten" the air, and kept in ventilated places. Medical gases, aerosols and flammable gases need separate storage. CQC also names medical gas storage in its list.
- Laundry. Bedding, towels and other linen are among the most common fuels the guide lists. Keep linen away from dryers and boilers and keep laundry rooms tidy.
- Kitchens. Cooking equipment is a common ignition source. The guide lists kitchen areas among the places to control hazards.
- Electrical equipment. Install, use and maintain equipment to the manufacturer's instructions. Include residents' own items brought from home.
- Bedding and furniture. The guide says products used for pressure care, such as mattress overlays, fleeces and underpads, should be resistant to ignition where possible.
- Arson and storage. Waste bins away from the building, nothing stored in escape routes or roof voids.
Expect the assessor to walk every area, including laundry, kitchen, plant rooms, stores and a sample of bedrooms. Agree access in advance so they don't miss anything.
What PEEPs, training and fire drills does a care home need?
Plan how each resident who needs help will be moved, train every member of staff in the evacuation strategy, and run drills that include night staff and night-time conditions.
PEEPs. The Home Office says a suitable emergency plan includes personal emergency evacuation plans for people who may need help to evacuate. The care guide adds that a resident's PEEP may need to be part of their care plan. A useful PEEP covers how the person is alerted, what equipment staff use, how many staff are needed and where the person goes. Update it whenever their needs change.
Training. The 2023 Home Office guide says high-risk premises such as care homes may need more frequent refresher training than the usual annual minimum. The care guide says training should cover:
- keeping fire doors closed, or closing them
- what to do on finding a fire and hearing the alarm
- calling the fire and rescue service
- using protected areas for horizontal evacuation
- when and how to use delayed evacuation
Drills. The Home Office says drills are likely to be needed at least annually and often more often, and that permanent night shift workers must take part. The care guide advises either one drill at night or one that simulates night conditions with night staffing levels, and including regular respite residents in some drills. In Scotland, guidance says drills should happen at least twice a year, with every staff member taking part at least once a year.
Records to keep
- The fire risk assessment, every review, and who carried them out
- Action plan with dates completed
- PEEPs for each resident who needs help
- Fire alarm, emergency lighting, extinguisher and door-release tests
- Drill records: date, time, staff on duty, time taken, problems found
- Staff training records, including night and agency staff
How do you choose an assessor and prepare for the visit?
Pick an assessor with real care home experience, agree the scope in writing, and have your floor plans, rotas, PEEPs and test records ready. Then act on the findings within the timescales set.
The Home Office says independent certification or registration is particularly important where people sleep or the premises serve vulnerable people. When you compare assessors, ask:
- How many care homes or nursing homes have you assessed, and can you give references?
- Are you certificated under a third-party scheme or registered with a professional body? Check the register yourself.
- Will you test our evacuation strategy against our night staffing, not just the building?
- Does your scope include roof voids, plant rooms and every bedroom type?
- Do you hold professional indemnity insurance?
The legal competence requirement for fire risk assessors (article 9A of the Fire Safety Order) is not yet in force. Choosing someone competent is still your responsibility, and the Home Office recommends you keep a record of how you chose. See how to choose a fire risk assessor and what affects the cost.
Before the visit, gather:
- Floor plans showing compartments, fire doors and protected areas.
- Number of beds per area and current residents' dependency.
- Day and night staffing levels.
- PEEPs, your fire procedure and evacuation plan.
- Service records for alarm, emergency lighting, extinguishers and door hold-open devices.
- Drill and training records, plus details of any recent building work.
Reviews. The law doesn't set a fixed interval, but the assessment must be reviewed regularly and whenever something significant changes. Scotland's guidance names changes in residents' dependency, new equipment, alterations and any fire or near miss.
Are the rules different in Scotland, Wales and Northern Ireland?
Yes. Scotland uses the Fire (Scotland) Act 2005 and has its own care home guidance. Wales uses the Fire Safety Order like England, but has its own care regulator. Northern Ireland has its own fire law and regulator.
- England: Fire Safety Order, enforced by fire and rescue authorities. The Home Office residential care guide is marked as applying to England. CQC regulates the care service.
- Wales: the Fire Safety Order also applies, so the duty to carry out and record the assessment is the same. Care homes are regulated by Care Inspectorate Wales, not CQC. Check Welsh Government and your fire and rescue service for any Wales-specific guidance.
- Scotland: the Fire (Scotland) Act 2005 and Fire Safety (Scotland) Regulations 2006 place duties on the "dutyholder", and the Scottish Fire and Rescue Service enforces them. The Scottish Government's practical fire safety guidance for existing care homes (February 2022) also serves as statutory guidance for the fire service. Because care homes need registration, the significant findings must be recorded.
- Northern Ireland: the Fire and Rescue Services (Northern Ireland) Order 2006 and the Fire Safety Regulations (Northern Ireland) 2010 apply. Care homes are regulated by the RQIA. Check NIFRS and RQIA for current requirements.
Whichever nation you are in, the core questions are the same: can the building contain a fire, can your staff move residents in time at night, and is the plan written down and practised?
Related guides
Care home fire risk assessments: frequently asked questions
Who is responsible for the fire risk assessment in a care home?
In England and Wales it is the responsible person under the Fire Safety Order. For a care home that is normally the registered provider as employer. A landlord who controls parts of the building, and contractors who maintain fire systems, can share duties for what they control.
Does CQC enforce fire safety in care homes?
No. Fire and rescue authorities enforce fire safety law. CQC regulates the safety and quality of care, asks care homes applying to register for a copy of their fire risk assessment, and checks safe premises under regulations 12 and 15.
What is progressive horizontal evacuation?
Staff move residents near the fire through a fire-resisting barrier into an adjoining protected area on the same floor. Residents wait there while the fire is dealt with, and move further only if needed. The Home Office says it is normally adopted in care homes.
How many night staff does a care home need for fire safety?
No fixed number is set in law. The Home Office guide says the fire risk assessment should identify how many staff are needed to carry out the emergency plan, and the number of beds in each protected area should depend on the minimum number of staff awake, normally the night shift.
Can we wait for the fire service to evacuate residents?
No. The Home Office guide says you should not depend on the fire and rescue service to evacuate people. Your plan must work with your own staff. Scottish guidance says the fire service should only need to rescue residents if the planned evacuation has failed.
Can care home fire doors be held open?
Yes, with the right device. The Home Office guide suggests door closers with an electromagnetic hold-open or free-swing function that release when the fire alarm sounds. Doors must never be wedged, and the guide says doors with these devices should be closed at night.
Does every resident need a PEEP?
Any resident who may need help to evacuate should have one. The Home Office says the emergency plan should include personal emergency evacuation plans for those people, and the care guide says a PEEP may need to be part of the resident's care plan.
How often should care homes hold fire drills?
In England the Home Office says at least annually and often more frequently, with night staff included. The care guide advises a drill at night or one simulating night conditions. Scottish guidance says at least twice a year, with every staff member taking part at least once a year.
How often should a care home fire risk assessment be reviewed?
The law sets no fixed interval but requires regular review, and review whenever something significant changes. In a care home that includes changes in residents' dependency, staffing, layout, building work, or after a fire or near miss. Your assessor should advise on frequency.
Can a care home manager do the fire risk assessment themselves?
The law allows anyone competent to do it. But the Home Office warns that experience of ordinary workplaces may not be enough for a residential care home. Many providers use an assessor with care home experience, and the provider stays legally responsible either way.
Sources
We checked the facts on this page against these sources on 14 November 2026:
- Home Office: Fire safety risk assessment: residential care premises
- Home Office: A guide for persons with duties under fire safety legislation
- CQC: Fire risk assessment (registration supporting documents)
- CQC: Regulation 12: Safe care and treatment
- CQC: Memorandum of understanding with the National Fire Chiefs Council
- Scottish Government: Fire safety - existing care homes: practical guidance
- legislation.gov.uk: Regulatory Reform (Fire Safety) Order 2005, article 9